Key Features
Programmable switch setting and analog scaling
3-in-1 capability: digital pressure gauge, switch and transducer
Ultra-compact design
Simple Push-button menu navigation
Easy local adjustments using 3 pushbuttons
Min. / Max. function records low and high pressure events
Markets & Applications
HVAC-R
Duct Flow
Blower Performance
Filter Monitoring
Velocity Pressure
Electrical Termination
Wire leads, PVC insulated
Output Signal
1-5 VDC (3-wire)
Display
3½ digit LED
Dampening
Digital by firmware setting
Ranges
Unidirectional: 50 Pa ... 5 kPa / 0.25 in. H2O ... 25 in. H2O
Bidirectional: ±50 Pa ... ±5 kPa / ±0.25 in. H2O ... ±25 in. H2O
Wetted Parts Material
Aluminum, Titanium, PBT, Buna, Glass, Gold, Silicone Rubber, Silicon, Silicone RTV & Brass. NOT FOR USE WITH LIQUIDS
Ingress Protection
IP40
Case or Body Material
Polycarbonate/ABS
Process Connection Location
Centre back
Mounting
Flush
Surface
Switch Style
NPN or PNP - Field programable
Process Connection Style
Barbed fitting
Accuracy
1.5% of span (URL)
Pressure Type
Differential pressure
Static Pressure
500 mbar / 7.5 psi