Key Features
Easy local adjustments using 3 pushbuttons
Ultra-compact design
3-in-1 capability: digital pressure gauge, switch and transducer
Programmable switch setting and analog scaling
Simple Push-button menu navigation
Min. / Max. function records low and high pressure events
Markets & Applications
HVAC-R
Velocity Pressure
Filter Monitoring
Blower Performance
Duct Flow
Switch Style
NPN or PNP - Field programable
Static Pressure
500 mbar / 7.5 psi
Ranges
Unidirectional: 50 Pa ... 5 kPa / 0.25 in. H2O ... 25 in. H2O
Bidirectional: ±50 Pa ... ±5 kPa / ±0.25 in. H2O ... ±25 in. H2O
Wetted Parts Material
Aluminum, Titanium, PBT, Buna, Glass, Gold, Silicone Rubber, Silicon, Silicone RTV & Brass. NOT FOR USE WITH LIQUIDS
Ingress Protection
IP40
Display
3½ digit LED
Case or Body Material
Polycarbonate/ABS
Process Connection Location
Centre back
Electrical Termination
Wire leads, PVC insulated
Mounting
Flush
Surface
Output Signal
1-5 VDC (3-wire)
Dampening
Digital by firmware setting
Process Connection Style
Barbed fitting
Accuracy
1.5% of span (URL)
Pressure Type
Differential pressure